QuikWater Hot Shot
The QuikWater Hot Shot is the new right-size solution for commercial applications that require hot water on demand with a smaller footprint. The Hot Shot delivers 6 to 16 gallons per minute of pure, potable, hot water on demand and is ideal for smaller meat packing plants, car washes, commercial laundries, and cafeteria, hospital and institutional kitchens. Engineered with our innovative clean-burn combustion technology, the Hot Shot uses a dry fire process that is safer than conventional boilers and operates with 99% energy efficiency. QuikWater manufactures all of its systems using the highest quality materials for extra long life and extra low maintenance.
The QuikWater Hot Shot is ideal for smaller meat packing plants, car washes, commercial laundries, and cafeteria, hospital and institutional kitchens.
When we say clean, we mean it.
While competitive products are designed with burner flames positioned directly in the falling water, QuikWater's patented clean-burn technology provides an isolated dry atmosphere – eliminating the safety risks associated with standard pressurized systems, and producing the highest fuel efficiency without water contamination or wear and tear on the shell materials.
QuikWater Hot Shot Direct-Contact Water Heating Systems
- 99% energy efficient; up to 40% energy savings
- Environmentally safe
- 6 GPM to 16 GPM of pure, potable hot water on demand
- Small footprint; ideal for commercial applications
- 200,000 btu/hr to 400,000 btu/hr with temperatures up to 180°F
- Fast ROI compared to boilers or indirect-contact water heating systems
- Patented clean-burn technology
- Non-pressurized design eliminates safety risks
- Runs on natural gas or propane
- Five-point utility installation
- Easy installation and maintenance
- Pre-piped, pre-wired, factory tested
- Plug-and-play system ships in one piece
- Small storage
- ETL/ETLC listed; UL compliant
Hot Shot Heater Capacities
Heater calculations:
Temp Rise x GPM x 500 = BTU Required
Temp Rise = Hot Water Temp – Cold Water Temp
| Temp. Rise | GPM per BTU Setting | ||
| 200,000 BTUs | 300,000 BTUs | 400,000 BTUs | |
| 30 | 13.3 | NA | NA |
| 40 | 10.0 | 15.0 | NA |
| 50 | 8.0 | 12.0 | 16.0 |
| 60 | 6.7 | 10.0 | 13.3 |
| 70 | 5.7 | 8.6 | 11.4 |
| 80 | NA | 7.5 | 10.0 |
| 90 | NA | 6.7 | 8.9 |
| 100 | NA | 6.0 | 8.0 |
| 110 | NA | 5.5 | 7.3 |
| 120 | NA | NA | 6.7 |
| Inlet Size: | 3/4" FNPT |
| Outlet Size: | 1" FNPT |
| Fuel Inlet Size: | 3/4" FNPT |
| Electrical Connection: | 230v single phase, 12 amp |
| Stack Connection Size: | 4" FNPT |

Download our QuikWater Hot Shot brochure or use our interactive selection guide to determine the right QuikWater system for your operation. To learn more about us and our products, or to experience QuikWater's direct-contact water heating systems first-hand, contact QuikWater to schedule our demo unit.